70mva Furnace Transformer

Product Details
Customization: Available
Certification: CE, ISO, CE, ISO
Customized: Customized
Manufacturer/Factory, Trading Company, Group Corporation
Gold Member Since 2007

Suppliers with verified business licenses

Type of Ownership
Limited Company
Plant Area
>2000 square meters
  • 70mva Furnace Transformer
  • 70mva Furnace Transformer
  • 70mva Furnace Transformer
  • 70mva Furnace Transformer
  • 70mva Furnace Transformer
  • 70mva Furnace Transformer
Find Similar Products

Basic Info.

Model NO.
70mva Furnace Transformer
Surface Treatment
Painted
Fuel
Gas Coal Electric, Electric
Range of Applications
Industrial, Industrial
Type
Cusomized, Eaf
Place Style
Vertical
Usage
Steel Molding
Transport Package
Nude, Wooden Cases
Specification
As per drawing
Trademark
Ville Industry
Origin
China
HS Code
851300020
Production Capacity
300units Per Year

Product Description

70mva electric arc furnace with serial reactor

Standard IEC 76, VDE 0532
Rated Power, nominal 70 MVA
Winding / oil temperature rise 55 / 50 °C
Operating Voltage / Frequency 33 kV / 50Hz
Rated lightning impulse withstand voltage 170 kV
Secondary Insulation Level, min. 4 kV
Impedance Voltage to be defined e.g. 6 up to 12 %
Output connection Closed delta Furnace Transformer Tap Changer
Tap Changer On-Load Number of taps 17 Secondary
voltage / current - Max. Sec Voltage 980 V - Ref. Sec. Voltage 550 V - Min. Sec. Voltage 400 V -
Max. current 61 kA Technical Description:
The operating voltage is set on the primary voltage side using a motor-operated onload tap changer. This tap changer is
installed inside the transformer tank in a separate compartment. Furnace Transformer Protective Facilities For the
transformer protection beside other, the following main equipment is foreseen: Buchholz protection Oil liquid level gage
with alarm contacts for the transformer main tank Water flow indicator with alarm contacts On Line Dissolved Gas Analyser.
The protection facilities feature either audible or visual signals. In the event of a fault, the transformer is immediately isolated
from the mains.
Furnace Transformer Cooling o Type of cooling OFWF o Cooler capacity 2 x100 % o Cooling water inlet temperature Max.
35 °C Technical Description: The windings of each ladle furnace transformer are cooled by the transformer oil. The
transformer will be provided with one-oil pumps and one double core heat exchanger. The oil-circulating pump conveys
the oil through an oil/water cooler, where the heat is transferred from the oil to the cooling water.


Serial Reactor

The transformer can be equipped with a serial reactor, which allows operating the furnace as high impedance furnace. The
reactor will be connected to the primary side of the transformer and will be equipped with off-load tap changer for optimization
of the different process stages. The reactor can be installed inside and outside of the ladle furnace transformer tank. Serial
reactor Main Data Type Air Insulated Phase Reactance 0 - 5 Ohm Tap changer On-load, Taps 5